Skip to main content

InformaCast Emergency Notification Settings

DialCast
Dial phone code in the format: 505#[BLDG NUM]

Message
Alert - [BLDG] Lockdown Message

Recipient Groups

  • [BLDG] - Lenel Panel On → Trigger Lenel relay on Barix
  • [BLDG] - Fire Panel On → Trigger Fire panel relay on Barix
  • [BLDG] - All → Send alert to all building phones and speakers
    • Includes [BLDG] - Mobile → Send alert building administrative staff
  • Admin - SRO Mobile → Send alert to district administrative staff and SRO

M2M Contact Closures
Lenel Input triggered on Barix relay

IP Address for Barix relays

Input Ports
[BLDG] Lenel Input - This is triggered from the Lenel panel relay

Message
Alert - [BLDG] Lockdown Message

Recipient Groups

  • [BLDG] - Fire Panel On → Trigger Fire panel relay on Barix
  • [BLDG] - All → Send alert to all building phones and speakers
    • Includes [BLDG] - Mobile → Send alert building administrative staff
  • Admin - SRO Mobile → Send alert to district administrative staff and SRO

Note: Do not include the "Lenel Panel On" relay because that is where the lockdown originated

 

Configure Output Ports for various relays

  • Relay 1 - Always Lenel Panel
  • Relay 2 - Always Fire Panel
  • Relay 3 - Available
  • Relay 4 - Available

A Barix relay might be setup just to control other devices like security curtains and not need a Lenel or Fire Panel configured.